Float condensate drains AOK

A float drain needs no electricity. The condensate level lifts a float, the float opens the valve, and it shuts before the air can follow the condensate out. Pure physics — nothing to set and nothing that can fail electrically.
Which AOK you need
Pressure and material decide. The brass units cover ordinary systems; the stainless ones are taken where the medium is more aggressive or the surroundings demand it.
| Float AOK drains — pressure, capacity and material | ||||||
|---|---|---|---|---|---|---|
| Order code | Draining | Working pressure | Min. pressure | Drain orifice | Outlet | Material |
| AOK13PA | 167 l/h | up to 13 bar | — | — | push-in fitting ø 8 mm | plastic |
| AOK16B | 120 l/h | up to 16 bar | — | — | push-in fitting ø 8 mm | brass |
| AOK20B | 167 l/h | up to 20 bar | — | 1.8 mm | G 1/2" | brass |
| AOK20SS | 167 l/h | up to 20 bar | — | 1.8 mm | G 1/2" | stainless steel |
| AOK50B | 145 l/h | up to 50 bar | 10 bar | 1.8 mm | G 1/2" | brass |
| AOK50SS | 145 l/h | up to 50 bar | 10 bar | 1.8 mm | G 1/2" | stainless steel |
The whole series works at +1.5 – +65 °C. Medium: air, water, oil and other non-aggressive media.
#showmore#
How a float drain works
Inside the body is a float. As condensate flows in the level rises and the float with it; at the upper mark it opens the valve mechanically and the condensate leaves. The level drops, the float drops with it and the valve shuts — and it manages that before the air reaches it.
It is all mechanical: no electronics, no sensor, nothing to set. That is both the advantage and the limit — a float knows nothing but the level, but it works where there is no socket.
Fitting
It goes under a filter, a tank or a cyclone separator — anywhere the condensate runs down. The smaller units go straight into filters, the larger ones under pressure vessels.
🔴 What to watch on the high-pressure ones
The 50 bar units have a minimum recommended working pressure of 10 bar. Below that the valve may not shut reliably. It is the commonest reason somebody buys the wrong unit — a high-pressure drain is not a „better version", it is a different product for different conditions.
Ventilek says
The float is the only one that works without a socket.
It has two big advantages: it needs no power and it cannot be set wrong, because there is nothing to set. But watch one thing people get caught by: a high-pressure float will not work below ten bar. If you have eight bar in the workshop, do not buy the fifty-bar unit thinking it is sturdier — it will not shut on you.
Frequently asked questions — float aok
- Does a float drain need electricity?
- No. It works purely mechanically — the level lifts a float and the float opens the valve. That is why it suits anywhere there is no socket by the compressor.
- Does a float drain lose air?
- It should not. The valve shuts before the air reaches it, because the float drops as soon as the level does.
- Can I use a high-pressure unit on an ordinary system?
- No. The high-pressure AOK units have a minimum recommended pressure of 10 bar — below that the valve may not shut reliably. Choose by the pressure you actually have.
- When should I take the stainless version?
- When the medium is more aggressive or the surroundings call for it — in food processing or chemistry, say. For ordinary compressed air, brass is enough.
Product sorting
List of products
The AOK13PA float drain releases condensate automatically, with no electricity and no setting up. It is fitted to the outside of the filter bowl. Up to 13 bar, 167 l/h at 7 bar.
The AOK16B float drain releases condensate automatically, with no electricity and no setting up. It is fitted inside the filter bowl. Up to 16 bar, 120 l/h at 7 bar.
A float condensate drain for filters, pressure vessels and cyclone separators. It works mechanically, without electricity and without setting. Body made of stainless steel.
A float condensate drain for filters, pressure vessels and cyclone separators. It works mechanically, without electricity and without setting. Body made of brass.
A float condensate drain for filters, pressure vessels and cyclone separators. It works mechanically, without electricity and without setting. Body made of stainless steel.
The AOK20B float drain releases condensate automatically, with no electricity and no setting up. It is fitted externally to the equipment and copes with large amounts of...