Proportional pressure regulators controlled by an electrical signal

Proportional regulators set the pressure of compressed air by an electrical signal – from a control system, PLC or another controller. The outlet pressure is proportional to the 0–10 V or 4–20 mA signal: half the signal means half the range. You can thus change the pressure during operation and remotely, without touching a knob.
You can choose from three series: the powerful DRPA by AirCom for flow rates of 210 / 700 / 1,400 l/min and pressures up to 16 bar, the compact ETV 3000 by EMC with a display and a flow rate of 1,150 l/min, and the DRPE with G 1/4", which is being phased out. All have a pressure sensor at the outlet that constantly monitors and corrects the pressure, protection rating IP 65 and an M12 connector.
What the proportional regulators offer
- you set the pressure by an electrical signal of 0–10 V or 4–20 mA – from a PLC, control system or setpoint device
- the outlet pressure follows the signal with a linearity of ± 0.5 % (DRPA) to ± 0.2 % (DRPE) of full scale
- pressure sensor at the outlet – the regulator constantly monitors and corrects the pressure
- the ETV 3000 shows the setpoint and actual pressure on its display and reports it via a 1–5 V signal, the DRPE via a 0–10 V signal
- venting as large as filling (DRPA up to 1,400 l/min) – the outlet pressure can also be reduced quickly
- power supply 15–24 V DC (DRPE) or 24 V DC (DRPA and ETV 3000), M12 connector, protection rating IP 65
- mounting bracket included with the DRPE and ETV 3000, angled M12 socket with the DRPA
- for high flow rates, it can control another remote-controlled regulator
- DRPA without own air consumption, also handles lubricated air; the control parameters can be set with software
Three series: DRPA, ETV 3000 and DRPE
The series differ in flow rate, control ranges and what else the regulator can do. For new machines, choose DRPA or ETV 3000 – DRPE is a series being phased out.
| Series | Manufacturer | Connection | Ranges | Flow rate | Actual pressure signal | Extras |
|---|---|---|---|---|---|---|
| DRPA | AirCom | G 1/8", G 1/4", G 1/2" | 0–6 to 0–16 bar | 210 / 700 / 1,400 l/min | — | no own air consumption, set-up by software, lubricated air |
| ETV 3000 | EMC | G 3/8" | 0.05–5 / 0.05–9 bar | 1,150 l/min | 1–5 V and display | display, setting by push buttons, bracket and foot included |
| DRPE | — | G 1/4" | 0–1 / 0–4 / 0–6 / 0–10 bar | 425 l/min | 0–10 V | series being phased out, DRSE cables |
DRPE is a series being phased out. A lower-cost replacement with a higher flow rate is the ETV 3000; for higher flow rates and pressures up to 16 bar, the DRPA. Please note: the ETV 3000 has a different connection (G 3/8"), a 24 V DC power supply and a 1–5 V output signal, and its inlet pressure must be at least 1 bar higher than the set pressure – check this when replacing a DRPE; we will be happy to advise.
DRPA proportional regulators (AirCom)

The DRPA works as a 3/2-way poppet valve with a proportional solenoid and digital control. It adds air to the outlet and releases it from there at the same flow rate – 210 / 700 / 1,400 l/min depending on the size – and consumes no air itself. It also handles lubricated air; filtration to 50 µm is sufficient.
You set the control parameters (zero point, range, ramp, gain) with the DRPA ANALYSE software; the software is not needed for normal operation. If the signal or power supply fails, the regulator vents the outlet.
| Connection | Control range | 0–10 V signal | 4–20 mA signal | Inlet pressure | Flow rate |
|---|---|---|---|---|---|
| G 1/8" | 0–6 bar | DRPA18-6 | — | max. 12 bar | 210 l/min |
| G 1/8" | 0–10 bar | DRPA18-10 | DRPA18-10-E20 | max. 12 bar | 210 l/min |
| G 1/4" | 0–6 bar | DRPA14-6 | — | max. 12 bar | 700 l/min |
| G 1/4" | 0–10 bar | DRPA14-10 | DRPA14-10-E20 | max. 12 bar | 700 l/min |
| G 1/4" | 0–16 bar | DRPA14-16 | DRPA14-16-E20 | max. 18 bar | 700 l/min |
| G 1/2" | 0–10 bar | DRPA12-10 | DRPA12-10-E20 | max. 12 bar | 1,400 l/min |
| G 1/2" | 0–12 bar | DRPA12-12 | DRPA12-12-E20 | max. 14 bar | 1,400 l/min |
Flow rate and venting according to the manufacturer at an inlet of 6 bar and an outlet of 5 bar. The inlet pressure should be at least 10 % higher than the highest pressure being set and must not exceed the stated value. Power supply 24 V DC ±10 %, current consumption max. 500 / 1,000 / 1,400 mA (G 1/8" / G 1/4" / G 1/2").
ETV 3000 proportional regulators with display (EMC)

The ETV 3000 is a compact proportional regulator with a G 3/8" connection and a flow rate of 1,150 l/min. The three-colour display shows the setpoint and actual pressure – in bar, MPa, kPa or psi – and you set the regulator with the push buttons directly on it.
It reports the actual pressure via a 1–5 V output signal. Power supply 21.6–26.4 V DC, current consumption max. 125 mA, protection rating IP 65, 4-pin M12 connector. An L-bracket and a foot for mounting are included.
Inlet pressure 1 to 10 bar, always at least 1 bar higher than the set pressure. The air must be finely filtered (5 µm) and oil-free.
| Control range | 0–10 V signal | 4–20 mA signal | Inlet pressure | Flow rate | Output signal |
|---|---|---|---|---|---|
| 0.05–5 bar | ETV3000-5 | ETV3000-5-E20 | 1 to 10 bar | 1,150 l/min | 1–5 V |
| 0.05–9 bar | ETV3000-9 | ETV3000-9-E20 | 1 to 10 bar | 1,150 l/min | 1–5 V |
DRPE series: four ranges, two types of signal

DRPE is a series being phased out, with a G 1/4" connection. Choose the range according to the highest pressure you will set. Each range comes in two versions depending on the control signal: codes ending in I are for 0–10 V voltage, codes ending in A for 4–20 mA current.
| Control range | 0–10 V signal | 4–20 mA signal | Inlet pressure | Flow rate |
|---|---|---|---|---|
| 0–1 bar | DRPE14-1I | DRPE14-1A | max. 2.1 bar | 425 l/min |
| 0–4 bar | DRPE14-4I | DRPE14-4A | max. 11.4 bar | 425 l/min |
| 0–6 bar | DRPE14-6I | DRPE14-6A | max. 11.4 bar | 425 l/min |
| 0–10 bar | DRPE14-10I | DRPE14-10A | max. 13.8 bar | 425 l/min |
The inlet pressure must be at least as high as the pressure being set and must not exceed the stated value – a higher pressure could damage the pressure sensor at the outlet.
All DRPE proportional regulators
| Code | Signal | Control range | Inlet pressure | Flow rate | Weight |
|---|---|---|---|---|---|
| DRPE14-1I | 0–10 V | 0–1 bar | max. 2.1 bar | 425 l/min | 0.8 kg |
| DRPE14-4I | 0–10 V | 0–4 bar | max. 11.4 bar | 425 l/min | 0.8 kg |
| DRPE14-6I | 0–10 V | 0–6 bar | max. 11.4 bar | 425 l/min | 0.8 kg |
| DRPE14-10I | 0–10 V | 0–10 bar | max. 13.8 bar | 425 l/min | 0.8 kg |
| DRPE14-1A | 4–20 mA | 0–1 bar | max. 2.1 bar | 425 l/min | 0.8 kg |
| DRPE14-4A | 4–20 mA | 0–4 bar | max. 11.4 bar | 425 l/min | 0.8 kg |
| DRPE14-6A | 4–20 mA | 0–6 bar | max. 11.4 bar | 425 l/min | 0.8 kg |
| DRPE14-10A | 4–20 mA | 0–10 bar | max. 13.8 bar | 425 l/min | 0.8 kg |
Connecting cables for DRPE
The cable for the DRPE regulator is ordered separately. Both have an M12 × 1 socket at the end and a length of 5 m. DRPA regulators come with an angled M12 socket (5 pins) for your own cable.
How to choose a proportional regulator
- Series according to flow rate. The DRPE delivers 425 l/min, the ETV 3000 1,150 l/min and the DRPA 210 / 700 / 1,400 l/min depending on the size (G 1/8", G 1/4", G 1/2"). For even higher flow rates, use the proportional regulator as a pilot for a large remote-controlled regulator.
- Range according to the highest pressure. Choose the smallest range whose upper limit is above the highest pressure you will set – in a smaller range, the same change in signal corresponds to a smaller change in pressure and control is finer. For a maximum of 3.5 bar, the 0–4 bar range (DRPE) or 0.05–5 bar (ETV 3000) is suitable; for 12 to 16 bar, only the DRPA.
- Signal according to the control system. If the control system has a 0–10 V voltage output, choose a code ending in I (DRPE) or a code without “E20” (DRPA, ETV 3000); for a 4–20 mA current output, a code ending in A (DRPE) or in “-E20”. A current signal is more resistant to interference on longer cable runs.
- Inlet pressure. For the DRPE, the inlet pressure may be no more than 2.1 bar for the 0–1 bar range, 11.4 bar for the 0–4 and 0–6 bar ranges and 13.8 bar for the 0–10 bar range. For the ETV 3000 it is 1 to 10 bar (at least 1 bar above the setting), for the DRPA 12 / 14 / 18 bar depending on the range.
- DRPE flow rate. The DRPE regulator itself delivers 425 l/min. For higher consumption, use it as a pilot regulator for a large remote-controlled regulator.
- Display and pressure feedback. If you want to see the pressure directly on the regulator, choose the ETV 3000 with display. The actual pressure is reported by an electrical signal from the ETV 3000 (1–5 V) and the DRPE (0–10 V).
Example: a press needs a contact pressure of 0.5 to 3.5 bar set from a PLC with a 4–20 mA analogue output. The ETV 3000 with the 0.05–5 bar range and a current signal is suitable – ETV3000-5-E20 – and it also shows the pressure on its display. In the DRPE series, which is being phased out, this is the 0–4 bar range with a current signal – DRPE14-4A – together with a connecting cable, for example with the angled connector DRSE-CW5. A large contact-pressure cylinder with a consumption of 1,200 l/min and a pressure of up to 10 bar is handled by the DRPA12-10-E20.
Not sure which regulator to choose? Try the pressure regulator selector – based on line pressure, required pressure and flow.
#showmore#
How a proportional regulator works

- The control signal comes in through the M12 connector. The electronics compare it with the pressure measured at the outlet by the sensor.
- If the pressure is lower than the signal corresponds to, the regulator adds air from the inlet. If it is higher, it releases the excess through the vent (DRPE up to 198 l/min, ETV 3000 up to 1,150 l/min, DRPA at the same flow rate as filling).
- The outlet pressure is directly proportional to the signal: 0 V or 4 mA means 0 bar, 10 V or 20 mA the upper limit of the range. For the 0–6 bar range, 5 V or 12 mA therefore corresponds to 3 bar.
- The DRPE reports the actual pressure via a 0–10 V output signal and the ETV 3000 via a 1–5 V signal – the control system can check that the pressure matches the setpoint.
- DRPE accuracy: linearity ± 0.2 %, repeatability ± 0.2 %, hysteresis 1 % and overall accuracy ± 0.5 % of full scale.
- The DRPA is driven by a proportional solenoid that directly opens the filling or venting poppet valve. The linearity and repeatability of the DRPA are ± 0.5 %, hysteresis below ± 1 %; the ETV 3000 has a linearity of ± 1 %, a repeatability of ± 0.5 % and a hysteresis of 0.5 %.



Electrical connection

- power supply 15–24 V DC, current consumption max. 325 mA
- 4-pin M12 connector (A-coded) on the side of the regulator
- control signal 0–10 V (codes ending in I) or 4–20 mA (codes ending in A)
- 0–10 V output signal for checking the actual pressure
- protection rating IP 65
- the 5 m connecting cable with M12 connector is ordered separately – with a straight connector DRSE-C5 or an angled one DRSE-CW5
The points above apply to the DRPE series. Electrical connection of all three series:
| Series | Power supply | Consumption | Connector | Signal | Output signal | Protection rating |
|---|---|---|---|---|---|---|
| DRPA | 24 V DC ±10 % | 500 / 1,000 / 1,400 mA | M12, 5 pins, angled socket included | 0–10 V / 4–20 mA | — | IP 65 |
| ETV 3000 | 24 V DC (21.6–26.4 V) | 125 mA | M12, 4 pins, A-coded | 0–10 V / 4–20 mA | 1–5 V | IP 65 |
| DRPE | 15–24 V DC | 325 mA | M12, 4 pins, A-coded, DRSE cable | 0–10 V / 4–20 mA | 0–10 V | IP 65 |
Installation

- install a fine compressed air filter upstream of the regulator – the air must be finely filtered (3 µm) and oil-free
- the mounting bracket is included – you can fix the regulator to pipework, a wall or in a control cabinet
- the inlet pressure must not exceed the value for the given range; for the 0–1 bar range (max. 2.1 bar at the inlet), install a standard pressure regulator upstream
- you can connect a pressure gauge via the G 1/8" thread; it is not included
- operating temperature −10 to +60 °C
The points on the left apply to the DRPE series. For the new series, also:
- the DRPA handles lubricated and non-lubricated air filtered to 50 µm; it can be mounted in any position, preferably vertically
- keep the inlet pressure at least 10 % above the highest pressure being set
- if the signal is on and there is no pressure at the inlet, the DRPA valve heats up – the manufacturer recommends monitoring the pressure with a pressure switch
- operating temperature of the DRPA 0 to +60 °C, of the ETV 3000 0 to +50 °C
- the ETV 3000 needs finely filtered (5 µm), oil-free air; the L-bracket and foot are included, and the venting exits through M5 and G 1/8" ports
Software for setting up the DRPA

The DRPAANALYSE software with an RS-232 converter shows the setpoint and actual pressure, records the control behaviour and lets you set the zero point, range, ramp and controller parameters (P, PI, PID). You can save the settings and use them for other regulators. The software is not needed for normal operation of the DRPA regulator.
High flow rate: proportional regulator as a pilot
The DRPE regulator itself delivers 425 l/min, the ETV 3000 1,150 l/min and the DRPA up to 1,400 l/min. If you need more air, connect its outlet to the pilot inlet of a remote-controlled DRI regulator: the large regulator then holds the pressure set by the proportional regulator, so you also control the high flow rate by an electrical signal. For very precise control, the FDRI03 precision regulator is suitable.

Specifications of the DRPE series
| Parameter | Value |
|---|---|
| Control signal | 0–10 V (codes ending in I) or 4–20 mA (codes ending in A) |
| Output signal | 0–10 V |
| Control ranges | 0–1 / 0–4 / 0–6 / 0–10 bar |
| Inlet pressure | at least the pressure being set, max. 2.1 / 11.4 / 11.4 / 13.8 bar |
| Flow rate | 425 l/min |
| Venting | 198 l/min |
| Linearity | ± 0.2 % of full scale |
| Repeatability | ± 0.2 % of full scale |
| Hysteresis | 1 % of full scale |
| Accuracy | ± 0.5 % of full scale |
| Power supply | 15–24 V DC, current consumption max. 325 mA |
| Electrical connection | M12 connector, A-coded, 4 pins |
| Protection rating | IP 65 |
| Connection | G 1/4", pressure gauge G 1/8" (pressure gauge not included) |
| Operating temperature | −10 to +60 °C |
| Medium | finely filtered compressed air (3 µm), oil-free, neutral gases |
| Material | aluminium, brass and plastic, NBR seals |
| Dimensions | 57 × 57 × 127 mm (width × depth × height) |
| Weight | 0.8 kg |
| Included | mounting bracket |
Specifications of the DRPA series
| Parameter | Value |
|---|---|
| Manufacturer | AirCom |
| Control signal | 0–10 V (input resistance 100 kΩ) or 4–20 mA (250 Ω) – codes with “-E20” |
| Control ranges | 0–6 / 0–10 / 0–12 / 0–16 bar depending on size |
| Inlet pressure | max. 12 / 14 / 18 bar (0–6 and 0–10 / 0–12 / 0–16 bar), at least 10 % above the setting |
| Connection | G 1/8", G 1/4", G 1/2" (bore 3 / 6 / 12 mm) |
| Flow rate and venting | 210 / 700 / 1,400 l/min (inlet 6 bar, outlet 5 bar) |
| Own air consumption | none |
| Linearity | < ± 0.5 % of full scale |
| Repeatability | ± 0.5 % of full scale |
| Hysteresis | < ± 1 % of full scale |
| Power supply | 24 V DC ±10 %, current consumption max. 500 / 1,000 / 1,400 mA |
| Electrical connection | M12 connector, A-coded, 5 pins, angled socket included |
| Protection rating | IP 65 with socket fitted |
| Operating temperature | 0 to +60 °C |
| Medium | dry, lubricated or non-lubricated compressed air filtered to 50 µm, neutral gases |
| Material | brass body (G 1/8" and G 1/4") or aluminium body (G 1/2"), internal parts brass and stainless steel, NBR seals |
| Dimensions (W × H × D) | 35 × 83 × 57 / 52 × 105 × 68 / 70 × 136 × 85 mm |
| Weight | 0.6–1.6 kg |
| In the event of signal or power failure | the outlet is vented |
| Parameter setting | DRPA ANALYSE software (accessory) |
Specifications of the ETV 3000 series
| Parameter | Value |
|---|---|
| Manufacturer | EMC |
| Control signal | 0–10 V or 4–20 mA (codes with “-E20”) |
| Output signal | 1–5 V |
| Control ranges | 0.05–5 / 0.05–9 bar |
| Inlet pressure | 1 to 10 bar, at least 1 bar higher than the set pressure |
| Connection | G 3/8", pressure gauge G 1/8" |
| Flow rate | 1,150 l/min (inlet 7 bar, outlet 6 bar, pressure drop 1 bar) |
| Venting | 1,150 l/min, M5 and G 1/8" ports |
| Linearity | ± 1 % of full scale |
| Repeatability | ± 0.5 % of full scale |
| Hysteresis | 0.5 % of full scale |
| Accuracy | ± 0.5 % of full scale |
| Power supply | 24 V DC (21.6–26.4 V), current consumption max. 125 mA |
| Electrical connection | M12 connector, A-coded, 4 pins |
| Protection rating | IP 65 |
| Display | setpoint and actual pressure, units bar, MPa, kPa or psi |
| Operating temperature | 0 to +50 °C |
| Medium | finely filtered compressed air (5 µm), oil-free, neutral gases |
| Weight | 0.6–0.55 kg |
| Included | L-bracket and foot |
Ventilek advises
Install the proportional regulator downstream of a filter. If the control system is far away, choose the 4–20 mA current signal – it is less susceptible to interference on long cable runs. Instead of the DRPE, choose the ETV 3000 today (lower cost, with display) or the DRPA (higher flow rate, pressure up to 16 bar).
- very precise manual control: FDR regulators
- pilot regulators: DRF regulators
- high flow rate remotely: DRI regulators
- standard pressure regulators: regulators 280 and 406
- What is the difference between codes ending in I and A?
- For the DRPE, only the control signal: I = 0–10 V voltage, A = 4–20 mA current. The ranges, flow rate and dimensions are the same. For the DRPA and ETV 3000, the 4–20 mA current signal is indicated by the suffix “-E20”.
- Does the regulator need a power supply?
- Yes. The DRPE needs 15–24 V DC with a current consumption of max. 325 mA, the DRPA and ETV 3000 24 V DC (DRPA consumption up to 1,400 mA, ETV 3000 max. 125 mA). The power supply and signals run through the M12 connector.
- What pressure may be at the inlet?
- For the DRPE, at least as much as you want to set, and no more than 2.1 bar for the 0–1 bar range, 11.4 bar for the 0–4 and 0–6 bar ranges and 13.8 bar for the 0–10 bar range. For the 0–1 bar range, you will therefore usually install a standard pressure regulator upstream. The ETV 3000 needs 1 to 10 bar (at least 1 bar more than you set), the DRPA no more than 12 / 14 / 18 bar depending on the range.
- Do I have to fit a pressure gauge to the regulator?
- No – the DRPE reports the actual pressure via the 0–10 V output signal, and the ETV 3000 shows it on its display. However, you can connect a pressure gauge via the G 1/8" thread (DRPE and ETV 3000); it is not included.
- Are the connecting cables included?
- Not with the DRPE. The 5 m cable with M12 connector is ordered separately – with a straight (DRSE-C5) or angled connector (DRSE-CW5). The DRPA comes with an angled M12 socket to which you connect your own cable.
- Can the regulator handle a higher flow rate?
- The DRPE delivers 425 l/min by itself, the ETV 3000 1,150 l/min and the DRPA up to 1,400 l/min. For more air, connect it as a pilot regulator for a large remote-controlled DRI regulator.
- What can replace the DRPE?
- DRPE is a series being phased out. A lower-cost replacement with a higher flow rate is the ETV 3000 with display (G 3/8", 0.05–5 or 0.05–9 bar); for higher flow rates and pressures up to 16 bar, the DRPA. Check the power supply (24 V DC), the connection and the output signal – the ETV 3000 reports the pressure via a 1–5 V signal.
- Do I need software for the DRPA?
- No, the regulator is factory-set and works without it. The DRPA ANALYSE software is useful if you want to adjust the zero point, range, ramp or control parameters, monitor the pressure curve or troubleshoot.
Technical data of the DRPE series according to current documentation (2026), of the DRPA series according to the catalogue of the manufacturer AirCom, of the ETV 3000 series according to documentation of the manufacturer EMC. Linearity, repeatability, hysteresis and accuracy are calculated from the upper limit of the control range.
You will find more regulators in the category air pressure regulators.
Product sorting
List of products
DRPE proportional pressure regulator: you set the outlet pressure by a 4–20 mA electrical signal from the control system.control range 0–1 bar, inlet pressure max. 2.1...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–10 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–16 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 4–20 mA electrical signal.control range 0–16 bar, inlet pressure...
DRPE proportional pressure regulator: you set the outlet pressure by a 4–20 mA electrical signal from the control system.control range 0–6 bar, inlet pressure max. 11.4...
DRPE proportional pressure regulator: you set the outlet pressure by a 4–20 mA electrical signal from the control system.control range 0–4 bar, inlet pressure max. 11.4...
DRPE proportional pressure regulator: you set the outlet pressure by a 0–10 V electrical signal from the control system.control range 0–6 bar, inlet pressure max. 11.4...
DRPE proportional pressure regulator: you set the outlet pressure by a 0–10 V electrical signal from the control system.control range 0–4 bar, inlet pressure max. 11.4...
DRPE proportional pressure regulator: you set the outlet pressure by a 0–10 V electrical signal from the control system.control range 0–10 bar, inlet pressure max. 13.8...
DRPE proportional pressure regulator: you set the outlet pressure by a 4–20 mA electrical signal from the control system.control range 0–10 bar, inlet pressure max. 13.8...
DRPE proportional pressure regulator: you set the outlet pressure by a 0–10 V electrical signal from the control system.control range 0–1 bar, inlet pressure max. 2.1 barcontrol...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–6 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–10 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 4–20 mA electrical signal.control range 0–10 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–6 bar, inlet pressure...
EMC ETV 3000 proportional pressure regulator with display: you set the outlet pressure by a 0–10 V electrical signal.control range 0.05–5 bar, inlet pressure 1 to 10 barcontrol...
EMC ETV 3000 proportional pressure regulator with display: you set the outlet pressure by a 4–20 mA electrical signal.control range 0.05–5 bar, inlet pressure 1 to 10 barcontrol...
EMC ETV 3000 proportional pressure regulator with display: you set the outlet pressure by a 0–10 V electrical signal.control range 0.05–9 bar, inlet pressure 1 to 10 barcontrol...
EMC ETV 3000 proportional pressure regulator with display: you set the outlet pressure by a 4–20 mA electrical signal.control range 0.05–9 bar, inlet pressure 1 to 10 barcontrol...
Connecting cable for DRPE proportional pressure regulators with an angled (90°) M12 × 1 socket.length 5 mPUR cable, 4 × 0.34 mm²angled 90° socket – the cable runs along the...
Connecting cable for DRPE proportional pressure regulators with a straight M12 × 1 socket.length 5 mPUR cable, 4 × 0.34 mm²straight socket – the cable runs perpendicular to the...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 4–20 mA electrical signal.control range 0–10 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–10 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 4–20 mA electrical signal.control range 0–10 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 0–10 V electrical signal.control range 0–12 bar, inlet pressure...
AirCom proportional pressure regulator of the DRPA series with digital control: you set the outlet pressure by a 4–20 mA electrical signal.control range 0–12 bar, inlet pressure...
Software with RS-232 converter for setting up AirCom DRPA proportional pressure regulators from a computer.display of the setpoint and actual pressuresetting of the zero point,...